NCDEQ Stormwater Design Manual — C-0. Minimum Design Criteria for all SCMs

StateNorth CarolinamediumNeeds review

This extraction needs human review.

Source is chapter C-0 only (MDC for all SCMs) of the multi-PDF NCDEQ Stormwater Design Manual. Required storm depth and SCM-specific MDC live in other parts/rules; this chapter states general sizing, outlet 10-year peak erosion protection, and lists example infiltrating SCM types. Peak-flow calculation methods and required software are not specified here (volume methods referred to Part B).

Fields not found in document: design_criteria.peak_flow_calculation_method, design_criteria.required_hydrologic_hydraulic_software
Other manuals in North Carolina: Charlotte-Mecklenburg

Document Metadata

Jurisdiction level
state

Rule 15A NCAC 2H .1050. MDC for All Stormwater Control Measures

Important Links, Page 1

State
North Carolina

NCDEQ Stormwater BMP Manual

Header

Version / edition
Revised: 1-3-2017

C-0. MDC for all SCMs 1 Revised: 1-3-2017

Page header

Adoption / effective date
2017-01-03

Revised: 1-3-2017

Page header

Last revised date
2017-01-03

Revised: 1-3-2017

Page header

Relationship to state manual
independent

This chapter contains Minimum Design Criteria (MDC) that apply to all Stormwater Control Measures (SCMs)... See Part C of this Manual for SCM-specific requirements.

Design Objective, Page 1

Design Criteria

Design storm return periods (years)
10-year

The outlets of SCMs shall be designed so that they do not cause erosion immediately downslope of the discharge point during the peak flow from the 10-year storm event as shown by engineering calculations.

GENERAL MDC 4: EROSION PROTECTION, Page 3

Water quality volume method
Combined design volume of all SCMs must handle the required storm depth for the applicable stormwater program (depth varies by rule). Example: Rule 15A NCAC 02H .1021(6) requires a one-inch storm depth for runoff treatment in non-coastal HQW and ORW management zones. Design volume accounts for build-out runoff from all surfaces draining to the system; off-site drainage may be bypassed. Volume calculation methods are in Part B of the full manual (not in this chapter).

The combined design volume of all SCMs on the project shall be sufficient to handle the required storm depth... Rule 15A NCAC 02H .1021(6) requires that for projects designed to achieve runoff treatment, the required storm depth is one inch for non-coastal HQW and ORW management zones.

GENERAL MDC 1. SIZING, Page 2

Peak flow calculation method(s)
Not found in document

No evidence cited

Required hydrologic/hydraulic software
Not found in document

No evidence cited

Approved BMP categories
Infiltration systems, Bioretention cells, Permeable pavement, Vegetated swales, Level spreader-filter strips, Berms, SCM-specific devices per Rules 15A NCAC 02H .1051–.1062 (Part C)

Some SCMs that allow water to infiltrate include: infiltration systems, bioretention cells, permeable pavement, and depending upon native soils, vegetated swales, level spreader-filter strips, and berms.

GENERAL MDC 2: CONTAMINATED SOILS, Page 2