City of Chesapeake
Stormwater Management and Drainage Design
Document Metadata
“Stormwater, for both water quantity and quality, shall be designed in general by the criteria established herein, the City's Master Drainage Plan”
Section 5.0 GENERAL
“the Virginia Department of Transportation Drainage Manual and the Virginia Stormwater Management Handbook”
Section 5.0 GENERAL
“Revised 12/16 STORMWATER MANAGEMENT & DRAINAGE DESIGN”
Page headers
No evidence cited
“Revised 12/16”
Page headers
“Stormwater, for both water quantity and quality, shall be designed in general by the criteria established herein, the City's Master Drainage Plan, the Virginia Department of Transportation Drainage Manual and the Virginia Stormwater Management Handbook. When there is a conflict between the Virginia Department of Transportation Drainage Manual, the Hampton Roads Planning District Commission Regional Construction Standards and these criteria, these criteria shall govern.”
Section 5.0 GENERAL A–B
Design Criteria
“24 Hour Rainfall Depths (NOAA's NWS)... 2-yr. 3.7" 5-yr. 5.0" 10-yr. 6.0" 25-yr. 7.0" 50-yr. 8.17" 100 9.44"”
Section 5.2 HYDROLOGY B, Page 5-5
“Virginia's proposed Stormwater Management Program (VSMP) Permit Regulations (4 VAC 50-60 et seq.) include water quality and quantity requirements based, in part, on the "Virginia Runoff Reduction Method" (VRRM).”
Section 5.4 B. Water Quality
“Storm drainage systems including Hydraulic Grade Line, etc. shall be designed using the rational method, for the recurrence frequency as follows”
Section 5.3 HYDRAULICS A.1
“25-yr. 7.0” 50-yr. 8.17” 100 9.44” C. Acceptable methods for runoff analysis are tabulated below: Model Major Sys. Minor Sys. Hydrologic Hydraulic Water Quality Hydrology Software HEC-GeoHMS X X HEC-HMS X X TR-55 X TR-20 X Pond Pack X X X WMS X X Watershed Modeling X X Hydrauli”
p. 5
“and/or maintenance. 4. Acceptable BMP Facilities: Post construction BMPs can be either Non-Proprietary BMPs or Proprietary/Manufactured BMPs. DEQ is currently evaluating Proprietary/Manufactured BMP’s for recommended efficiencies; there are no approved Proprietary/Man”
p. 18