City of Bismarck
Stormwater Design Standards Manual
This extraction is flagged for quality review.
Compare each cited field to the official PDF before relying on it. What this means
Peak discharge storms, water quality requirements (0.5 in / 80% TSS), NRCS methods, and acceptable software are explicitly stated. Prescriptive Vwq sizing details are in appendix Reference 5-2, not reproduced in main text. Pipeline excerpt repair removed 1 unlocated citation(s).
Document Metadata
“Municipal Public Works Improvements Bismarck, North Dakota” available from the office of the City Engineer. Stormwater Management Plan (SWMP) A written document detailing stormwater runoff characteristics for a defined area and the management of that runoff to mitigate advers”
p. 15
“Municipal Public Works Improvements Bismarck, North Dakota” available from the office of the City Engineer. Stormwater Management Plan (SWMP) A written document detailing stormwater runoff characteristics for a defined area and the management of that runoff to mitigate advers”
p. 15
No evidence cited
“for activities constructed after January 1, 2018 that meet one or more of the following criteria: 1. Land disturbance greater than or equal to 3,000 square feet and less than 10,000 square feet, occurring on land with slopes of less than 12 percent; or”
p. 21
No evidence cited
“The goal of this section is to provide guidance on the design, performance, and analysis requirements of the City of Bismarck regarding Post-Construction Peak Discharge Compliance.”
Section 4.0, Page 4-1
Design Criteria
“Post-Construction runoff resulting from the 2-, 5-, 10-, and 100-year 24-hour rainfall events shall not exceed the runoff rate of the existing conditions.”
Table 4-1, Page 4-1
“Design BMPs to treat the first 0.5 inches of runoff from impervious areas. 80% Total Suspended Solids (TSS) removal on an average annual basis shall be achieved.”
Table 5-1, Page 5-1
“NRCS (SCS) Curve Number (CN) Method, NRCS Unit Hydrograph Methods & Time of Concentration Methods. The Rational Method is not an accepted methodology for Peak Discharge Control Compliance.”
Section 4.4.1, Page 4-9
“1. HydroCAD 2. InfoSWMM 3. XP-SWMM / XP-STORM 4. Storm & Sanitary Analysis (SSA) 5. Bentley CivilStorm 6. Civil 3D Hydrographs 7. HEC-HMS”
Reference 4-4, Appendix 4
“5.3.1 DETENTION BASINS ... 5.3.2 INFILTRATION BMPS ... 5.3.3 FLOW THROUGH BMPS”
Section 5.3, Pages 5-5 to 5-7